Effective Electrical Safety Comes Down to Two Factors: Engaged Leadership and Technical Awareness
Andrew Cochran, Contributor
Continuous improvement is a way of life for any business and is accepted as a standard approach in improving quality, productivity, and processes. At the core of continuous improvement is defining root causes, planning and executing preventative action to eliminate the potential issue, and deploying technology and practices that minimize the impact of any issue or hazard.
This approach to continuous improvement can be extended to electrical safety and is sorely needed.
Ask any executive, operations manager, or health and safety professional and the very first priority in dealing with a potentially negative issue is to prevent the issue from occurring whenever possible. The second priority is to minimize the impact should the negative event occur.
This structured approach is consistent with the Hierarchy of Control and is consistent with the updated language in NFPA 70E Annex 0 General Design Requirements 0.2.2:
Design option decision should facilitate the ability to eliminate hazards or reduce risk by doing the following:
- Reducing the likelihood of exposure
- Reducing the magnitude, or severity of exposure
- Enabling achievement of an electrically safe work condition
This is where the need for engaged leadership is required. We need to be asking the fundamental question, “have we as an organization taken steps to reduce the likelihood of exposure and/or reduce the magnitude of exposure, rather, or have we settled for protection and awareness only?”
Many industrial companies have taken the approach of conducting an arc flash study, or some form of electrical risk assessment, posting the resultant warning labels, purchasing PPE, and then stopped. The result is warning labels informing of a dangerous situation, but no proactive measures to reduce the likelihood of exposure or to mitigate the magnitude of the hazard. Engaged leadership can only be effective if there is technical awareness within the organization to answer the question: “what can we do to lower our risk and lower the hazard level?”
Consultants, facility managers, and maintenance personnel (the very people engaged leadership would turn to and ask the question) were asked two questions related to arc flash and electrical safety:
What in your opinion is the leading cause of arc flash incidences?
– Three phase faults
– Ground faults
– In-line faults
– Phase to phase faults
What is the best means to minimize the arc flash hazard?
– High-Resistance Grounding
– Optical Detection
– Labels and warnings
– PPE
The results are a cause for concern at several levels; only 50% of respondents correctly identified that the majority of arc flash incidents start as ground faults and yet 268 of these chose labels of PPE as the best means to minimize the arc flash hazard. Posting warnings, conducting awareness training, and purchasing and issuing PPE does not in any way reduce the likelihood of an arc flash event, nor does it reduce the magnitude of the arc flash. For those professing that PPE does reduce the severity of exposure, let’s pause and consider what it means to wear ARC-rated clothing – there is a 50% probability of receiving second-degree burns over 50% of your body; surely, we can’t accept this is safe.
This is why engaged leadership is not enough; there is a need for technical awareness also to achieve an effective electrical safety program and a safe electrical workplace.
When designing an electrical grounding system for an industrial operation for voltages of 1000 volts and below, there are three basic choices – ungrounded, solidly grounded, or resistance grounded – a technical decision.
Absent ground faults, any of the three options are reliable and safe, but ground faults are a reality in any electrical system and so the question becomes― does the grounding system choice affect the likelihood of experiencing an arc flash incident?
Control the Likelihood of Exposure
The first and obvious step is to de-energize the electric circuit before conducting any work whenever practical. If this isn’t practical or safe, then consider options that reduce the likelihood of an arc flash event occurring.
Again, referring to NFPA 70E, Annex 0 clause, “A great majority of electrical faults are of the phase-to-ground type. High-resistance grounding will insert an impedance in the ground return path and below (at 5kV nominal or below), leaving insufficient fault energy and thereby helping reduce the arc flash hazard level.”
This is consistent with statements in the Industrial Power System Grounding Design Handbook which states that 95% of all electrical faults are phase to ground faults and IEEE141-1993 Recommended Practice for Electric Power Distribution for Industrial Plants 7.2.2 which states “there is no arc flash hazard (on HRG systems) as there is with solidly grounded systems, since the current is limited to approximately 5 amps.”
In FM Global Standard 5-18 Protection of Electrical Equipment Single Phase and Other Related Faults it states, “Sustained arcing faults in low-voltage apparatus are often initiated by a single-phase fault to ground which results in extensive damage to switchgear and motor control centers.”
If we already understand that most arcing faults start as single-phase to-ground faults, (whether the specifics are 95% or the great majority) and that by employing High-Resistance Grounding (a technology that has been around for 50 years and used in all manner of industries, from petro-chemical to food processing, automotive, paper manufacturing, and data centers), we can reduce the exposure to the hazard significantly. The question then needs to be asked, “Why is this not the standard practice for grounding industrial facilities?”
HRG as a technology is recommended by IEEE, it is recognized by NFPA 70E, it is promoted by FM Global, and yet it is still not the default option when making the grounding decision for industrial facilities. One reasoning may simply be lack of technical awareness.
Of course, High-Resistance Grounding does not protect against phase-to-phase faults nor does it lower the incident energy calculation and therefore additional control steps must be taken to ensure an electrically safe workplace.
Reduce the Magnitude of Exposure
Again, referring to NFPA 70E, Annex 0 clause states “Arc flash relay. An arc flash relay typically uses light sensors to detect the light produced by an arc flash event. Once a certain level of light is detected, the relay will issue a trip signal to an upstream overcurrent device.”
An arc is developed in milliseconds and leads to the discharge of enormous amounts of energy. The energy discharged in the arc is directly proportional to the square of the short circuit current and the time the arc takes to develop, i.e., energy = I2t.
The damage resulting from the arc depends on the arcing current and time. Of these two factors, time is the most easily controlled and managed. Rules of thumb for different arc burning times are:
- 35ms or less – no significant damage to persons or switchgear which can often be returned to use after checking for insulation resistance.
- 100ms – small damage to switchgear that requires cleaning and possibly some minor repair. Personnel could be at risk of injuries.
- 500ms – catastrophic damage to equipment and personnel are likely to suffer serious injuries.
The goal of arc mitigation technology is to protect personnel and property. To effectively accomplish this, we must first detect the arc, and then cut the flow of current to the arc in as short a time as possible. As noted above, the target is to achieve a total reaction time of 100ms or less from detection of the arc to isolation of the circuit.
Arcs produce light at intensity levels that exceed 20,000 lux. This can be detected through special arc detection optical sensors connected to a relay system that has a typical operating time under 1ms and is the fastest arc flash detection technology currently available. The operating time is independent of the fault current magnitude since any current detector elements are used only to supervise the optical system.
With optical arc protection technology installed, the relay operating time is essentially negligible compared to the circuit breaker operating time. The cost is also fairly low since current transformers are only needed on the main breakers. If we sum up the circuit breaker operating time and the optical arc detection time, we are well below the goal of 100ms (regardless of the age and speed of the circuit breaker) and have mitigated the damage to a lower and safer level.
Simply changing from standard coordination and instantaneous settings on the relay (suggested by some consultants as sufficient) to a protection system which uses optical arc detection that incident energy levels are reduced substantially.
A workplace where the likelihood of an arc flash is significantly lower, where the impact of an arc flash can be minimized to very low levels is possible today – we just need engaged leadership and technical awareness.
Unintended Benefit of HRG Technology:
One industrial client who made the conversion from solidly grounded to HRG technology as a means of reducing the arc flash risk found the unintended but welcomed benefit of lower maintenance costs related to motor repair.
In fact, the savings in motor repair costs provided payback for the HRG system in 24 months.
This leading company, through engaged leadership and with technical awareness, lowered its risk of an arc flash from occurring and lowered operational costs at the same time.
What is stopping you from achieving the same results, engaged leadership or technical awareness? WMHS
Andrew Cochran is President at I-Gard Corporation, an industry leader in workplace electrical safety, with a focus on protection from ground faults and arc flash. Cochran joined the company in 1997 having previously held operational roles in companies such as Polaroid, ITT Automotive, and Stanley. At I-Gard he is responsible for setting the company’s strategic direction and focuses on driving progress in ensuring workplace electrical safety issues are addressed through technology and awareness.
Share on Socials!
Solving Safety Hazards and Shortcomings with Switch-Rated Plugs and Receptacles
Trimble Announces Next Generation Mixed-Reality Device with Microsoft HoloLens 2 Technology for Front-Line Workers in Construction, Oil and Gas, Manufacturing and Mining
Who And What Do You Trust with Your Electrical Safety?
Leaders in Electrical Safety
• Aramark
• Bowtie Engineering
• Enespro
• Ericson
• I-Gard Corporation
• IRISS
• KERMEL, INC.
• Lakeland Industries
• MELTRIC Corporation
• National Safety Apparel
• National Technology Transfer
• Oberon
• Saf-T-Gard
• SEAM Group
Subscribe!
Sign up to receive our industry publications for FREE!